Bergeron line

Bergeron line represents finite propagation delay and traveling-wave behavior through conductor-domain characteristic impedances and delayed histories.

Typical use

  • Use it to reproduce the electrical path between sources, converters, machines, and loads.

  • Keep phases, terminal orientation, connection type, and SI/per-unit parameter bases consistent.

This model represents a conductor-selective Bergeron transmission line for EMT studies. It reduces the full NABC line data to the enabled conductors, so it can represent configurations such as A, AB, AC, ABC, NA, NAB, and NABC.

Purpose

It is the EMT transmission-line template used when finite wave travel time must be represented without moving to a full frequency-dependent line model.

Behavior

  • Uses the enabled neutral and phase terminal voltages at both ends of the line.

  • Computes terminal current injections at both ends.

  • Stores delayed history terms that represent wave travel from one end of the line to the other.

  • Uses characteristic-impedance relations together with one propagation delay.

Characteristics

  • EMT traveling-wave line model.

  • Conductor-domain representation using the selected subset of NABC.

  • More detailed than an algebraic or lumped branch model, but simpler than a full JMarti-type frequency-dependent line.

How it works

The Bergeron method represents the active conductor system through a reduced characteristic-impedance matrix and one propagation delay. At each time step, the current injected at one terminal depends on the present terminal-voltage vector and on delayed current history arriving from the opposite end. This captures finite travel time, conductor coupling, and reflections efficiently.

Characteristic equations

Representative Bergeron relations are:

i_f(t) = \frac{v_f(t)}{Z_c} + I_{h,t}(t-\tau)

i_t(t) = \frac{v_t(t)}{Z_c} + I_{h,f}(t-\tau)

where the history terms carry the delayed traveling-wave information from the opposite terminal.

Interface table

Category

Name

Meaning

Units

Input

v_f_N

From-side neutral terminal voltage when the neutral conductor is active

pu

Input

v_f_A

From-side phase-A terminal voltage used by the Bergeron line equations when phase A is active

pu

Input

v_f_B

From-side phase-B terminal voltage used by the Bergeron line equations when phase B is active

pu

Input

v_f_C

From-side phase-C terminal voltage used by the Bergeron line equations when phase C is active

pu

Input

v_t_N

To-side neutral terminal voltage when the neutral conductor is active

pu

Input

v_t_A

To-side phase-A terminal voltage used by the Bergeron line equations when phase A is active

pu

Input

v_t_B

To-side phase-B terminal voltage used by the Bergeron line equations when phase B is active

pu

Input

v_t_C

To-side phase-C terminal voltage used by the Bergeron line equations when phase C is active

pu

Output

if_N

Current injected by the line at the from-side neutral port when active

pu

Output

if_A

Current injected by the line at the from-side phase-A port

pu

Output

if_B

Current injected by the line at the from-side phase-B port

pu

Output

if_C

Current injected by the line at the from-side phase-C port

pu

Output

it_N

Current injected by the line at the to-side neutral port when active

pu

Output

it_A

Current injected by the line at the to-side phase-A port

pu

Output

it_B

Current injected by the line at the to-side phase-B port

pu

Output

it_C

Current injected by the line at the to-side phase-C port

pu

Variable

Ih_f_N

From-side neutral-conductor history current after one travel delay

pu

Variable

Ih_f_A

Bergeron history current seen from the from-side phase-A port after one travel delay

pu

Variable

Ih_f_B

Bergeron history current seen from the from-side phase-B port after one travel delay

pu

Variable

Ih_f_C

Bergeron history current seen from the from-side phase-C port after one travel delay

pu

Variable

Ih_t_N

To-side neutral-conductor history current after one travel delay

pu

Variable

Ih_t_A

Bergeron history current seen from the to-side phase-A port after one travel delay

pu

Variable

Ih_t_B

Bergeron history current seen from the to-side phase-B port after one travel delay

pu

Variable

Ih_t_C

Bergeron history current seen from the to-side phase-C port after one travel delay

pu

Variable

history_buffer_f

Runtime delay buffer that stores from-side wave-history samples between EMT steps

sample history

Variable

history_buffer_t

Runtime delay buffer that stores to-side wave-history samples between EMT steps

sample history

Parameter

R_reduced

Reduced series-resistance matrix used in the Bergeron line companion form

pu

Parameter

L_reduced

Reduced series-inductance matrix used in the Bergeron line companion form

pu

Parameter

Zc_reduced

Reduced characteristic-impedance matrix used to relate terminal voltages and traveling-wave currents

pu

Parameter

tau_delay

Wave travel time used by the history update logic

s

Only the rows for enabled conductors are instantiated. All reduced matrices and history vectors follow the same active-conductor ordering at both line ends.

How to use it

  • Use it when propagation delay and wave reflection matter in EMT line studies.

  • Prefer simpler EMT line blocks when the line is short enough that travel-time effects are negligible for the study objective.