BESS

BESS represents an energy resource and its interface controls. Storage and photovoltaic models combine source-side energy or power limits with converter commands, so available active power, DC voltage, and reactive-power control must remain mutually consistent.

Typical use

  • Use it to study renewable or storage response to voltage, frequency, and power-reference disturbances.

  • Respect energy, current, DC-voltage, and active/reactive capability limits during initialization.

This model represents an EMT battery energy storage system with converter control and DC-side dynamics.

Purpose

It is a Level-1 averaged-value grid-following Battery Energy Storage System EMT template.

Behavior

  • Uses three AC phase voltages as external inputs.

  • Contains an internal battery block, imported VSC electrical/DC block, PLL, outer loop, inner current loop, and dq0/abc interface block.

  • Produces three-phase current injections into the EMT network.

  • Internally couples DC storage behavior with converter and AC-side control behavior.

Characteristics

  • Aggregated EMT BESS model.

  • More detailed than the RMS battery template.

  • Still averaged rather than switching-level.

Interface table

Category

Name

Meaning

Units

Input

v_A

Phase-A AC terminal voltage at the BESS connection point

pu

Input

v_B

Phase-B AC terminal voltage at the BESS connection point

pu

Input

v_C

Phase-C AC terminal voltage at the BESS connection point

pu

Output

i_A

Phase-A current injected into the EMT network by the BESS

pu

Output

i_B

Phase-B current injected into the EMT network by the BESS

pu

Output

i_C

Phase-C current injected into the EMT network by the BESS

pu

Variable

battery block

Internal averaged battery/DC-source submodel

submodel

Variable

vsc block

Internal averaged converter electrical/DC submodel

submodel

Variable

pll block

Internal synchronous-reference-frame PLL submodel

submodel

Variable

outer loop block

Internal BESS outer control loop submodel

submodel

Variable

inner loop block

Internal converter current-control submodel

submodel

Variable

transformer block

Internal dq0/abc interface branch block

submodel

Parameter

battery Thevenin parameters

Internal battery open-circuit-voltage and resistance-related parameters

mixed

Parameter

battery SoC parameters

State-of-charge, efficiency, and energy-capacity-related parameters

mixed

Parameter

converter parameters

Imported VSC electrical, DC-link, current-limit, and control parameters

mixed

How to use it

  • Use this template for EMT studies of converter-based battery energy storage connected to an AC network.

  • It is a plant-level averaged model, not a switching cell-level battery/converter model.