Complete generatorο
Complete generator belongs to an electromechanical machine or prime-mover model. It links electrical torque and flux with rotor speed, angle, mechanical power, or actuator dynamics, making it central to frequency, voltage, and rotor-angle stability studies.
Typical useο
Use it when electrical transients must interact with rotating mass or machine controls.
Initialize torque, power, flux, and speed consistently with the solved power flow.
This model represents a complete EMT synchronous generator with its machine and control blocks already connected.
Purposeο
It is a packaged phase-domain synchronous generator assembled from:
Sauer-Pai generator block,
exciter block,
governor block,
stabilizer block.
Behaviorο
Uses three-phase terminal voltages as external inputs.
Produces three-phase current injections as external outputs.
Internally wires machine, exciter, governor, and stabilizer signals together.
Uses the governor for mechanical torque, the exciter for field voltage, and the stabilizer as an auxiliary damping signal for the exciter.
Characteristicsο
EMT abc-domain composite generator.
Suitable for detailed synchronous-machine transient studies.
More detailed than the RMS
Complete generator.
Block structureο
Terminal voltages (v_A, v_B, v_C)
-> Sauer-Pai generator
<- Exciter (v_f)
<- Governor (Tm)
-> Stabilizer input (omega)
Stabilizer
-> Exciter auxiliary input
Machine outputs
-> i_A, i_B, i_C
Characteristic equationsο
Interface tableο
Category |
Name |
Meaning |
Units |
|---|---|---|---|
Input |
|
Terminal phase-A voltage applied to the composite generator |
pu |
Input |
|
Terminal phase-B voltage applied to the composite generator |
pu |
Input |
|
Terminal phase-C voltage applied to the composite generator |
pu |
Output |
|
Phase-A current injected into the EMT network by the composite generator |
pu |
Output |
|
Phase-B current injected into the EMT network by the composite generator |
pu |
Output |
|
Phase-C current injected into the EMT network by the composite generator |
pu |
Variable |
|
Internal synchronous-machine submodel |
submodel |
Variable |
|
Internal field-voltage controller submodel |
submodel |
Variable |
|
Internal mechanical-power controller submodel |
submodel |
Variable |
|
Internal damping controller submodel |
submodel |
Parameter |
|
Machine base angular frequency exposed through the wrapper mapping |
rad/s |
Parameter |
|
Wrapper-exposed resistance-related machine parameter |
pu |
Parameter |
|
Wrapper-exposed positive-sequence reactance-related machine parameter |
pu |
Parameter |
|
Wrapper-exposed zero-sequence reactance parameter |
pu |
Parameter |
|
Wrapper-exposed shared governor power-reference parameter |
pu |
How to use itο
Use this template when you want a full EMT synchronous generator already wired with its main control blocks.
Use the separate component documents when you want to understand the machine, exciter, governor, or stabilizer in isolation.