Complete generator

Complete generator belongs to an electromechanical machine or prime-mover model. It links electrical torque and flux with rotor speed, angle, mechanical power, or actuator dynamics, making it central to frequency, voltage, and rotor-angle stability studies.

Typical use

  • Use it when electrical transients must interact with rotating mass or machine controls.

  • Initialize torque, power, flux, and speed consistently with the solved power flow.

This model represents a complete EMT synchronous generator with its machine and control blocks already connected.

Purpose

It is a packaged phase-domain synchronous generator assembled from:

  • Sauer-Pai generator block,

  • exciter block,

  • governor block,

  • stabilizer block.

Behavior

  • Uses three-phase terminal voltages as external inputs.

  • Produces three-phase current injections as external outputs.

  • Internally wires machine, exciter, governor, and stabilizer signals together.

  • Uses the governor for mechanical torque, the exciter for field voltage, and the stabilizer as an auxiliary damping signal for the exciter.

Characteristics

  • EMT abc-domain composite generator.

  • Suitable for detailed synchronous-machine transient studies.

  • More detailed than the RMS Complete generator.

Block structure

Terminal voltages (v_A, v_B, v_C)
    -> Sauer-Pai generator
        <- Exciter (v_f)
        <- Governor (Tm)
        -> Stabilizer input (omega)
Stabilizer
    -> Exciter auxiliary input
Machine outputs
    -> i_A, i_B, i_C

Characteristic equations

\frac{d\theta_{abs}}{dt} = \omega_b \omega

\frac{d\omega}{dt} = \frac{T_m - T_e - D(\omega - \omega_s)}{2H}

T_e = \frac{3}{2}(\psi_d i_q - \psi_q i_d)

p_e = v_A i_A + v_B i_B + v_C i_C

q_e = \frac{1}{\sqrt{3}}\left((v_A-v_B)i_C + (v_B-v_C)i_A + (v_C-v_A)i_B\right)

Interface table

Category

Name

Meaning

Units

Input

v_A

Terminal phase-A voltage applied to the composite generator

pu

Input

v_B

Terminal phase-B voltage applied to the composite generator

pu

Input

v_C

Terminal phase-C voltage applied to the composite generator

pu

Output

i_A

Phase-A current injected into the EMT network by the composite generator

pu

Output

i_B

Phase-B current injected into the EMT network by the composite generator

pu

Output

i_C

Phase-C current injected into the EMT network by the composite generator

pu

Variable

Sauer-Pai generator block

Internal synchronous-machine submodel

submodel

Variable

Exciter block

Internal field-voltage controller submodel

submodel

Variable

Governor block

Internal mechanical-power controller submodel

submodel

Variable

Stabilizer block

Internal damping controller submodel

submodel

Parameter

omega_base

Machine base angular frequency exposed through the wrapper mapping

rad/s

Parameter

R1

Wrapper-exposed resistance-related machine parameter

pu

Parameter

X1

Wrapper-exposed positive-sequence reactance-related machine parameter

pu

Parameter

X0

Wrapper-exposed zero-sequence reactance parameter

pu

Parameter

generator_share_p_ref

Wrapper-exposed shared governor power-reference parameter

pu

How to use it

  • Use this template when you want a full EMT synchronous generator already wired with its main control blocks.

  • Use the separate component documents when you want to understand the machine, exciter, governor, or stabilizer in isolation.