DC line

DC line represents passive network physics through resistance, inductance, capacitance, coupling, or switching topology. Its equations enforce voltage-current constitutive relations and therefore affect energy storage, damping, propagation, fault current, or grounding behavior.

Typical use

  • Use it to reproduce the electrical path between sources, converters, machines, and loads.

  • Keep phases, terminal orientation, connection type, and SI/per-unit parameter bases consistent.

This model represents a DC line with distributed electrical parameters for EMT studies.

Purpose

It is the EMT DC branch used to transfer current and power between two DC nodes while preserving electrical dynamics such as current ramping through line inductance.

Behavior

  • Uses from-side and to-side DC terminal voltages as inputs.

  • Computes the line current flowing between the two terminals.

  • Injects equal and opposite currents into the DC nodes.

  • May also expose one power-command channel in variants where the line is embedded inside a higher-level controlled DC transfer setup.

Characteristics

  • EMT DC branch model.

  • Suitable for converter-to-converter DC interconnections.

  • Can represent both resistive loss and current-dynamic effects.

How it works

The line current evolves according to the voltage difference across the branch and the series electrical parameters. Resistance dissipates power while inductance prevents instantaneous current changes. The current computed inside the branch is then exported as current injections at the two DC terminals.

Characteristic equations

L_{dc}\frac{di_{line}}{dt} = v_{f,dc} - v_{t,dc} - R_{dc} i_{line}

i_{f,dc} = -i_{line}, \qquad i_{t,dc} = i_{line}

p_{line} = (v_{f,dc} - v_{t,dc}) i_{line}

Interface table

Category

Name

Meaning

Units

Input

v_f_dc

From-side DC terminal voltage applied to the line model

pu

Input

v_t_dc

To-side DC terminal voltage applied to the line model

pu

Input

p_cmd

Power-transfer command used by the power-input DC line variant selected by the catalogue

pu

Output

i_f_dc

Current injected by the line into the from-side DC node

pu

Output

i_t_dc

Current injected by the line into the to-side DC node

pu

Variable

i_line

Internal branch current carried by the DC line between the two terminals

pu

Variable

p_line

Instantaneous power transferred through the DC line model

pu

Parameter

R_dc

Series resistance of the DC line branch

pu

Parameter

L_dc

Series inductance of the DC line branch when dynamic current evolution is enabled

pu

How to use it

  • Use it for EMT studies of DC links, DC feeders, or converter-to-converter DC interconnections.

  • Use a simpler algebraic connection only when DC current dynamics are not important.