Exciterο
Exciter belongs to an electromechanical machine or prime-mover model. It links electrical torque and flux with rotor speed, angle, mechanical power, or actuator dynamics, making it central to frequency, voltage, and rotor-angle stability studies.
Typical useο
Use it when electrical transients must interact with rotating mass or machine controls.
Initialize torque, power, flux, and speed consistently with the solved power flow.
This model represents the EMT excitation control block used with the complete generator model.
Purposeο
It is the EMT excitation controller built by get_exciter_emt().
Behaviorο
Receives machine exciter-feedback quantity, three-phase terminal voltages, and stabilizer signal.
Builds a voltage-magnitude measurement from the three phase voltages.
Filters the measurement and forms a regulated voltage error.
Applies lead-lag AVR action, limit logic, and field-stage dynamics.
Produces the field-voltage signal sent to the machine block.
Characteristicsο
EMT excitation control block.
Includes voltage filtering, AVR dynamics, limiter logic, and nonlinear field feedback.
Block structureο
abc voltage measurement
-> voltage magnitude Vm
-> voltage filter
-> reference / PSS error
-> lead-lag AVR
-> limiter and field feedback
-> field stage
-> Vf
Characteristic equationsο
Interface tableο
Category |
Name |
Meaning |
Units |
|---|---|---|---|
Input |
|
Exciter-feedback quantity received from the machine block |
pu |
Input |
|
Phase-A terminal voltage used by the exciter voltage-magnitude measurement |
pu |
Input |
|
Phase-B terminal voltage used by the exciter voltage-magnitude measurement |
pu |
Input |
|
Phase-C terminal voltage used by the exciter voltage-magnitude measurement |
pu |
Input |
|
Stabilizer signal received from the stabilizer block |
pu |
Output |
|
Field-voltage signal sent to the machine block |
pu |
Variable |
|
Measured voltage magnitude used by the AVR |
pu |
Variable |
|
Internal exciter-field variable after limiter action |
pu |
Variable |
|
Voltage reference used by the AVR loop |
pu |
Variable |
|
Voltage-measurement filter state |
pu |
Variable |
|
Rate-feedback state/output variable |
pu |
Variable |
|
Lead-lag internal state |
pu |
Variable |
|
AVR internal state |
pu |
Variable |
|
Dynamic ceiling variable used by one limiter stage |
pu |
Variable |
|
Auxiliary nonlinear field-feedback variable |
pu |
Parameter |
|
AVR gain |
pu/pu |
Parameter |
|
Rate-feedback gain |
pu/pu |
Parameter |
|
AVR stage time constant |
s |
Parameter |
|
Lead-lag lag time constant |
s |
Parameter |
|
Lead-lag lead time constant |
s |
Parameter |
|
Field-stage time constant |
s |
Parameter |
|
Rate-feedback time constant |
s |
Parameter |
|
Voltage measurement filter time constant |
s |
Parameter |
|
Demagnetizing/field-feedback factor |
pu |
Parameter |
|
Field-feedback coefficient |
pu |
Parameter |
|
Field conversion factor |
pu |
Parameter |
|
Saturation-law shaping coefficient |
pu |
Parameter |
|
Saturation-law exponential coefficient |
1/pu |
Parameter |
|
Exponential field-feedback coefficient |
pu |
Parameter |
|
Exponential field-feedback exponent coefficient |
1/pu |
Parameter |
|
Threshold at which the nonlinear field saturation becomes active |
pu |
Parameter |
|
Upper AVR output limit |
pu |
Parameter |
|
Lower AVR output limit |
pu |
Parameter |
|
Upper field-output related limit |
pu |
Parameter |
|
Upper internal exciter-field limit |
pu |
Parameter |
|
Lower internal exciter-field limit |
pu |
How to use itο
Treat this as the field-voltage control block of the EMT
Complete generatorpackage.It is not a standalone source or sink for the network.