Exponential load

Exponential load describes how electrical demand responds to terminal voltage. Its active- and reactive-power exponents produce different fault and recovery behavior, so the selected formulation materially changes system damping and voltage stability.

Typical use

  • Use the formulation that matches the time scale and measured behavior of the represented demand.

  • Initialize active and reactive demand from the power flow and verify the voltage-dependence convention.

This is a phase-selective EMT model. Any non-empty subset of A, B, and C can be enabled, with star or delta connection behavior selected independently. ABC is the default arrangement, not a restriction of the model.

Model behavior

Each active branch uses a second-order generalized integrator (SOGI) to obtain in-phase and quadrature voltage components. For branch X,

\dot u_X=k_{sogi}\omega(v_X-u_X)-\omega q_X,

\dot q_X=\omega u_X.

The filtered magnitude is regularized close to zero voltage:

V_X=\sqrt{u_X^2+q_X^2+\varepsilon}.

Active and reactive demand then follow

P_X=P_{0,X}\left(\frac{V_X}{V_0}\right)^a,
\qquad
Q_X=Q_{0,X}\left(\frac{V_X}{V_0}\right)^b.

The branch current is reconstructed from the filtered voltage components and the requested complex power. Internal safe denominators keep the expression finite during deep voltage depressions.

Phase and connection configurations

  • Star configurations create one load branch for every enabled phase. The reference can be grounded, externally neutral-connected, or a solved floating star point.

  • Delta configurations create branches only between enabled phase pairs and require at least two active phases.

  • Disabled conductors do not create ports, equations, states, or external mappings.

The generic branch notation in the equations and table applies equally to A, AB, AC, BC, ABC, and the applicable neutral-inclusive star interfaces.

Exponent selection

An exponent of 0 gives constant power, 1 gives approximately constant current, and 2 gives constant impedance in terms of power-versus-voltage magnitude. Active and reactive demand may use different exponents. Use measured composite-load behavior where available instead of assuming the same exponent for both.

Initialization and numerical behavior

The SOGI states are initialized from the solved branch voltages and the power setpoints from the operating point. Confirm that V0, P0_X, and Q0_X use the same base and sign convention as the connected device. The eps regularization prevents division by zero but does not make a constant-power load physically realistic at zero voltage; inspect fault recovery results when small terminal voltages are expected.

Interface table

Category

Name

Meaning

Units

Input

v_A

Instantaneous phase-A terminal voltage when phase A is active in the load

pu

Input

v_B

Instantaneous phase-B terminal voltage when phase B is active in the load

pu

Input

v_C

Instantaneous phase-C terminal voltage when phase C is active in the load

pu

Output

i_A

Phase-A current drawn by the exponential load and injected into the EMT network with load sign convention

pu

Output

i_B

Phase-B current drawn by the exponential load and injected into the EMT network with load sign convention

pu

Output

i_C

Phase-C current drawn by the exponential load and injected into the EMT network with load sign convention

pu

Variable

u_A

In-phase SOGI state used to estimate the filtered phase-A voltage component

pu

Variable

u_B

In-phase SOGI state used to estimate the filtered phase-B voltage component

pu

Variable

u_C

In-phase SOGI state used to estimate the filtered phase-C voltage component

pu

Variable

q_A

Quadrature SOGI state used to estimate the filtered phase-A voltage component

pu

Variable

q_B

Quadrature SOGI state used to estimate the filtered phase-B voltage component

pu

Variable

q_C

Quadrature SOGI state used to estimate the filtered phase-C voltage component

pu

Variable

V_A

Filtered magnitude of the phase-A voltage used in the exponential power law

pu

Variable

V_B

Filtered magnitude of the phase-B voltage used in the exponential power law

pu

Variable

V_C

Filtered magnitude of the phase-C voltage used in the exponential power law

pu

Variable

P_A

Active power absorbed on phase A after applying the voltage exponent

pu

Variable

P_B

Active power absorbed on phase B after applying the voltage exponent

pu

Variable

P_C

Active power absorbed on phase C after applying the voltage exponent

pu

Variable

Q_A

Reactive power absorbed on phase A after applying the voltage exponent

pu

Variable

Q_B

Reactive power absorbed on phase B after applying the voltage exponent

pu

Variable

Q_C

Reactive power absorbed on phase C after applying the voltage exponent

pu

Variable

i_A

Algebraic phase-A current computed from the phase-A power and voltage

pu

Variable

i_B

Algebraic phase-B current computed from the phase-B power and voltage

pu

Variable

i_C

Algebraic phase-C current computed from the phase-C power and voltage

pu

Parameter

V0

Reference voltage magnitude used in the exponential active- and reactive-power laws

pu

Parameter

a

Exponent that makes active power vary with voltage magnitude

dimensionless

Parameter

b

Exponent that makes reactive power vary with voltage magnitude

dimensionless

Parameter

k_sogi

SOGI gain that sets the filter tracking aggressiveness

dimensionless

Parameter

eps

Small regularization term used to avoid singular behavior near zero voltage

pu

Parameter

omega

Angular frequency used by the SOGI filter states

rad/s

Parameter

P0_A

Nominal phase-A active power at the reference voltage V0

pu

Parameter

P0_B

Nominal phase-B active power at the reference voltage V0

pu

Parameter

P0_C

Nominal phase-C active power at the reference voltage V0

pu

Parameter

Q0_A

Nominal phase-A reactive power at the reference voltage V0

pu

Parameter

Q0_B

Nominal phase-B reactive power at the reference voltage V0

pu

Parameter

Q0_C

Nominal phase-C reactive power at the reference voltage V0

pu

Only rows belonging to enabled phases are instantiated. For a delta model, the same quantities are associated with active phase pairs rather than phase-to-neutral branches.

How to use it

  1. Enable the required phases and choose the physical star or delta connection.

  2. Map the nominal branch powers and reference voltage from the initialized network.

  3. Set a and b from the intended voltage response.

  4. Verify the initial total active and reactive power, including the load/injection sign.

  5. Apply a small voltage disturbance before relying on severe-fault results, and confirm that the selected exponents give the expected response.