EMT faultο
EMT fault inserts a switchable low-impedance path at an internal node of a composed EMT branch model. Its algebraic equations preserve the series voltage path and split the through current from the selected fault current.
Typical useο
Insert it inside an EMT line or other explicitly composed branch model.
Select a phase mask consistent with the requested fault topology.
Keep all resistance and conductance settings on the parent EMT per-unit base.
The EMT fault is an internal branch-composition block for inserting a switchable low-impedance path at a three-phase EMT node. It is available from the dynamic editor library under Faults only while the editor is in EMT mode. It is not an RMS model and it is not mapped directly to a network device; it must be wired inside a parent EMT branch model, such as a line composition.
Supported topologiesο
Topology |
Required phases |
Electrical representation |
|---|---|---|
|
Exactly one of A, B or C |
Selected phase to ground through |
|
Exactly two phases |
One phase-to-phase path through |
|
Exactly two phases |
Each phase to a common node through |
|
A, B and C |
Three equal paths through |
|
A, B and C |
Each phase independently to ground through |
An invalid phase/topology combination is rejected when the template is built.
Series-insertion interfaceο
For every selected phase X, the block exposes four ports:
Direction |
Port |
Meaning |
Units |
|---|---|---|---|
Input |
|
Voltage arriving from the outer/upstream segment |
p.u. |
Input |
|
Current arriving from the inner/downstream segment |
p.u. |
Output |
|
Voltage passed to the inner/downstream segment |
p.u. |
Output |
|
Current returned to the outer/upstream segment |
p.u. |
The block owns both equations needed at its split node:
Consequently, the parent composition only connects these explicit ports; it must not add a second voltage-continuity equation.
Fault paths and switchingο
The binary mode fault_closed_mode selects the effective conductance. For a
phase path and a ground path respectively,
where m is fault_closed_mode, R_f is fault_r, R_g is fault_rg, and
G_open is fault_open_g. All resistance and conductance values are per-unit
on the parent EMT model base; the block performs no SI/base conversion.
For LLG, positive phase currents enter the common node and the ground current
leaves it, so the common-node equation is
Control and parametersο
Setting |
Meaning |
Units/default |
|---|---|---|
|
Initial value of |
|
|
Closed phase-path resistance |
|
|
Closed ground-path resistance |
|
|
Leakage conductance while open |
|
|
Adds the |
|
|
Fault closes when |
|
|
Saved compatibility parameter; not used by the present algebraic model |
|
Resistances and the compatibility time constant must be finite and positive; the open conductance must be finite and non-negative.
When signal control is disabled, events may change fault_closed_mode
directly. When it is enabled, the procedural logic samples fault_cmd and
writes the mode according to command_threshold.
Placement sideο
FromSide and ToSide describe where the user intends to place the fault in a
composed branch. The setting is retained in the internal editor projection and
is restored after saving and reopening. It does not automatically discover or
rewire a neighbouring line block: the outer and inner ports remain explicit,
so the parent model author controls the actual connection.
The internal diagram mirrors the selected topology, including the series port path, phase-to-phase link, floating common node, or grounded common node as applicable.