Full pseudo converterο
Full pseudo converter represents a power-electronic conversion or modulation function. Converter models translate control references into AC/DC electrical quantities, while averaged and switched variants retain different levels of switching detail and therefore require different simulation time steps.
Typical useο
Use averaged models for control and system studies, and switched models when waveform detail matters.
Coordinate reference frames, modulation limits, DC-side energy, and current-control bandwidth.
This model represents a controlled EMT converter with detailed modulation and switching-function behavior short of device-level switching.
Model structureο
The full pseudo converter is a hierarchical, averaged three-wire ABC model. It includes terminal measurements, a PLL, outer reference control, dq current control, modulation limits, an equivalent series filter, and an AC/DC power interface. It retains converter and controller dynamics without generating discrete PWM pulses.
This level of detail is useful when converter controls must interact with phase-domain network transients but switching harmonics are outside the study scope.
Characteristic behaviorο
The measured ABC quantities are transformed into the PLL-aligned dq0 frame. The equivalent filter-current states follow representative equations of the form
The outer controller converts active/reactive-power or DC-voltage error into current references. The inner controller converts current error into dq voltage commands, with current, modulation, and anti-windup limits. The dq currents are transformed back to ABC current injections. Idc is obtained from the AC/DC power balance and configured losses.
Averaged-model boundaryο
The voltage command is continuous: there is no carrier, gate pulse, or semiconductor switching transition. The model therefore captures controller bandwidth, filter dynamics, saturation, unbalance at the AC terminals, and DC-side interaction, but not PWM ripple, switching-frequency resonance, dead time, or device stress. Use the Switched converter when those effects are required.
Initialization and numerical behaviorο
The solved AC power flow and DC voltage establish the initial dq currents, PLL angle, controller integrators, and modulation command. R_eq, L_eq, ratings, references, and voltage bases must describe the same interface. Confirm that the initial current and voltage command are below their limits; an initially saturated controller often indicates inconsistent data rather than a meaningful transient.
The required time step is normally governed by the filter and fastest controller state, not by a PWM carrier. A time-step convergence check is still required for fast control or weak-grid studies.
Interface tableο
Category |
Name |
Meaning |
Units |
|---|---|---|---|
Input |
|
Instantaneous phase-A AC terminal voltage applied to the converter interface |
pu |
Input |
|
Instantaneous phase-B AC terminal voltage applied to the converter interface |
pu |
Input |
|
Instantaneous phase-C AC terminal voltage applied to the converter interface |
pu |
Input |
|
DC terminal voltage seen by the converter electrical block |
pu |
Output |
|
Phase-A current injected by the converter into the EMT network |
pu |
Output |
|
Phase-B current injected by the converter into the EMT network |
pu |
Output |
|
Phase-C current injected by the converter into the EMT network |
pu |
Output |
|
DC current drawn from or supplied to the DC terminal by the converter |
pu |
Variable |
|
Internal DC-link voltage state used by the electrical converter block |
pu |
Variable |
|
Instantaneous active power measured at the AC side of the converter |
pu |
Variable |
|
Instantaneous reactive power measured at the AC side of the converter |
pu |
Variable |
|
Instantaneous voltage angle estimated at the converter AC terminal |
rad |
Variable |
|
Instantaneous peak AC voltage magnitude estimated at the converter AC terminal |
pu |
Variable |
|
Internal phase angle produced by the converter PLL |
rad |
Variable |
|
Internal electrical frequency estimated by the converter PLL |
pu |
Variable |
|
Integral state of the PLL frequency loop |
pu |
Variable |
|
d-axis current reference produced by the outer control loop |
pu |
Variable |
|
q-axis current reference produced by the outer control loop |
pu |
Variable |
|
d-axis voltage command produced by the inner current loop |
pu |
Variable |
|
q-axis voltage command produced by the inner current loop |
pu |
Variable |
|
d-axis converter current inside the dq0 control frame |
pu |
Variable |
|
q-axis converter current inside the dq0 control frame |
pu |
Variable |
|
d-axis converter terminal voltage inside the dq0 control frame |
pu |
Variable |
|
q-axis converter terminal voltage inside the dq0 control frame |
pu |
Parameter |
|
DC-link capacitance used by the internal electrical block |
pu s |
Parameter |
|
Base electrical angular frequency used across the imported control blocks |
rad/s |
Parameter |
|
Proportional gain of the PLL controller |
pu/pu |
Parameter |
|
Integral gain of the PLL controller |
pu/(pu s) |
Parameter |
|
Equivalent series resistance used in the current-control decoupling equations |
pu |
Parameter |
|
Equivalent series inductance used in the current-control decoupling equations |
pu |
How to use itο
Connect the ABC and DC ports and solve the initial operating point.
Map ratings, AC filter data, DC-link data, references, limits, and all controller gains.
Check PLL alignment, dq current signs, and the AC/DC power balance at initialization.
Apply small reference or voltage steps before severe faults to verify control polarity and saturation behavior.
Select this model for control interaction studies; select the switched model only when waveform-level switching detail justifies its smaller time step.