Governorο
Governor belongs to an electromechanical machine or prime-mover model. It links electrical torque and flux with rotor speed, angle, mechanical power, or actuator dynamics, making it central to frequency, voltage, and rotor-angle stability studies.
Typical useο
Use it when electrical transients must interact with rotating mass or machine controls.
Initialize torque, power, flux, and speed consistently with the solved power flow.
This model represents the EMT governor block used with the complete generator model.
Purposeο
It is the EMT mechanical-power controller built by get_governor_emt().
Behaviorο
Receives rotor-speed and electromagnetic-torque feedback.
Forms a speed error around the speed reference.
Builds a torque order around a mechanical-power reference.
Limits the commanded mechanical torque and sends it to the machine block.
Characteristicsο
Compact EMT governor model.
Includes first-order governor dynamics and output saturation.
Used as the mechanical control block of the composite generator.
Block structureο
omega -> speed error
-> gain K and first-order governor state
-> torque order
-> saturation (Pmin/Pmax)
-> Tm
Characteristic equationsο
Interface tableο
Category |
Name |
Meaning |
Units |
|---|---|---|---|
Input |
|
Rotor-speed signal received from the machine block |
pu |
Input |
|
Electromagnetic torque signal received from the machine block |
pu |
Output |
|
Mechanical torque command sent to the machine block |
pu |
Variable |
|
Internal mechanical-power reference |
pu |
Variable |
|
Main governor state |
pu |
Variable |
|
Saturated torque-order variable |
pu |
Parameter |
|
Governor gain |
pu/pu |
Parameter |
|
Maximum mechanical torque or power command |
pu |
Parameter |
|
Minimum mechanical torque or power command |
pu |
Parameter |
|
Reserved maximum closing-rate parameter kept in the EMT governor API |
pu/s |
Parameter |
|
Reserved maximum opening-rate parameter kept in the EMT governor API |
pu/s |
Parameter |
|
Reserved auxiliary time parameter kept in the EMT governor API |
s |
Parameter |
|
Reserved proportional control gain kept in the EMT governor API |
model units |
Parameter |
|
Reserved integral control gain kept in the EMT governor API |
model units |
Parameter |
|
Speed reference |
pu |
Parameter |
|
Initial active-power scheduling parameter |
pu |
Parameter |
|
Small active-power offset parameter |
pu |
Parameter |
|
Main governor time constant |
s |
Parameter |
|
Secondary governor time parameter retained by the EMT governor API |
s |
How to use itο
Treat this as the mechanical controller of the EMT
Complete generatorpackage.It is not meant to be used as a standalone network device.