Governor

Governor belongs to an electromechanical machine or prime-mover model. It links electrical torque and flux with rotor speed, angle, mechanical power, or actuator dynamics, making it central to frequency, voltage, and rotor-angle stability studies.

Typical use

  • Use it when electrical transients must interact with rotating mass or machine controls.

  • Initialize torque, power, flux, and speed consistently with the solved power flow.

This model represents the EMT governor block used with the complete generator model.

Purpose

It is the EMT mechanical-power controller built by get_governor_emt().

Behavior

  • Receives rotor-speed and electromagnetic-torque feedback.

  • Forms a speed error around the speed reference.

  • Builds a torque order around a mechanical-power reference.

  • Limits the commanded mechanical torque and sends it to the machine block.

Characteristics

  • Compact EMT governor model.

  • Includes first-order governor dynamics and output saturation.

  • Used as the mechanical control block of the composite generator.

Block structure

omega -> speed error
      -> gain K and first-order governor state
      -> torque order
      -> saturation (Pmin/Pmax)
      -> Tm

Characteristic equations

e_\omega = \omega_{ref} - \omega

T_{ord} = P_{m,ref} + y_{gov0}

\frac{dy_{gov0}}{dt} = \frac{K e_\omega + (T_e - P_{m,ref}) - y_{gov0}}{T_1}

y_{2,3} = \mathrm{sat}(T_{ord}, P_{min}, P_{max})

T_m = y_{2,3}

Interface table

Category

Name

Meaning

Units

Input

omega

Rotor-speed signal received from the machine block

pu

Input

Te

Electromagnetic torque signal received from the machine block

pu

Output

Tm

Mechanical torque command sent to the machine block

pu

Variable

Pm_ref

Internal mechanical-power reference

pu

Variable

y_gov0

Main governor state

pu

Variable

y2_3_gov

Saturated torque-order variable

pu

Parameter

K

Governor gain

pu/pu

Parameter

Pmax

Maximum mechanical torque or power command

pu

Parameter

Pmin

Minimum mechanical torque or power command

pu

Parameter

Uc

Reserved maximum closing-rate parameter kept in the EMT governor API

pu/s

Parameter

Uo

Reserved maximum opening-rate parameter kept in the EMT governor API

pu/s

Parameter

T_aux

Reserved auxiliary time parameter kept in the EMT governor API

s

Parameter

Kp

Reserved proportional control gain kept in the EMT governor API

model units

Parameter

Ki

Reserved integral control gain kept in the EMT governor API

model units

Parameter

omega_ref

Speed reference

pu

Parameter

p0

Initial active-power scheduling parameter

pu

Parameter

P0

Small active-power offset parameter

pu

Parameter

T1

Main governor time constant

s

Parameter

T3

Secondary governor time parameter retained by the EMT governor API

s

How to use it

  • Treat this as the mechanical controller of the EMT Complete generator package.

  • It is not meant to be used as a standalone network device.