Ideal converterο
Ideal converter represents a power-electronic conversion or modulation function. Converter models translate control references into AC/DC electrical quantities, while averaged and switched variants retain different levels of switching detail and therefore require different simulation time steps.
Typical useο
Use averaged models for control and system studies, and switched models when waveform detail matters.
Coordinate reference frames, modulation limits, DC-side energy, and current-control bandwidth.
This model represents an averaged EMT converter with abc current injection and DC power balance.
Purposeο
It is an averaged EMT converter with abc current injection and DC power balance.
Behaviorο
Uses three-phase AC bus voltages and DC bus voltage as inputs.
Synthesizes phase currents from active and reactive power commands.
Computes DC current from the active-power balance.
Does not represent switching, PLL dynamics, filter dynamics, detailed inner current loops, or transformer detail.
Characteristicsο
Simple and computationally light EMT converter.
Better suited to control-oriented EMT studies than hardware-detail studies.
Good starting point when switching detail is unnecessary.
Characteristic equationsο
Representative equations are:
Interface tableο
Category |
Name |
Meaning |
Units |
|---|---|---|---|
Input |
|
Instantaneous phase-A AC terminal voltage |
pu |
Input |
|
Instantaneous phase-B AC terminal voltage |
pu |
Input |
|
Instantaneous phase-C AC terminal voltage |
pu |
Input |
|
DC bus voltage applied to the converter model |
pu |
Output |
|
Injected phase-A current sent to the AC network |
pu |
Output |
|
Injected phase-B current sent to the AC network |
pu |
Output |
|
Injected phase-C current sent to the AC network |
pu |
Output |
|
DC current implied by the converter active-power balance |
pu |
Variable |
|
Internal synchronous angle used to synthesize abc current references |
rad |
Variable |
|
Active-power reference used by the averaged converter logic |
system-base power |
Variable |
|
Reactive-power reference used by the averaged converter logic |
system-base power |
Variable |
|
DC-voltage reference used when DC-voltage regulation is active |
pu |
Variable |
|
Algebraic phase-A output current variable |
pu |
Variable |
|
Algebraic phase-B output current variable |
pu |
Variable |
|
Algebraic phase-C output current variable |
pu |
Variable |
|
Algebraic DC current variable |
pu |
Variable |
|
Measured instantaneous active power at the AC interface |
pu or system-base power |
Variable |
|
Measured instantaneous reactive power at the AC interface |
pu or system-base power |
Parameter |
|
Converter loss term added on top of transferred active power |
system-base power |
Parameter |
|
Scheduled base active-power seed used by the control-reference resolver |
system-base power |
Parameter |
|
Base angular frequency used to evolve the internal synchronous angle |
rad/s |
Parameter |
|
System base power used to normalize power commands |
MVA or system-base power |
Parameter |
|
First control mode selector |
code |
Parameter |
|
Second control mode selector |
code |
Parameter |
|
Target value associated with the first control mode |
mode-dependent |
Parameter |
|
Target value associated with the second control mode |
mode-dependent |
Parameter |
|
Initial AC voltage angle reference coming from the PF/EMT bridge |
rad |
Parameter |
|
Initial AC peak voltage magnitude used for current synthesis and initialization |
pu |
Parameter |
|
Nominal DC voltage used by the control-reference resolver |
pu |
How to use itο
Use it for simple EMT converter studies where only averaged current injection is required.
Do not use it when switching harmonics or detailed converter hardware effects matter.