Ideal converter

Ideal converter represents a power-electronic conversion or modulation function. Converter models translate control references into AC/DC electrical quantities, while averaged and switched variants retain different levels of switching detail and therefore require different simulation time steps.

Typical use

  • Use averaged models for control and system studies, and switched models when waveform detail matters.

  • Coordinate reference frames, modulation limits, DC-side energy, and current-control bandwidth.

This model represents an averaged EMT converter with abc current injection and DC power balance.

Purpose

It is an averaged EMT converter with abc current injection and DC power balance.

Behavior

  • Uses three-phase AC bus voltages and DC bus voltage as inputs.

  • Synthesizes phase currents from active and reactive power commands.

  • Computes DC current from the active-power balance.

  • Does not represent switching, PLL dynamics, filter dynamics, detailed inner current loops, or transformer detail.

Characteristics

  • Simple and computationally light EMT converter.

  • Better suited to control-oriented EMT studies than hardware-detail studies.

  • Good starting point when switching detail is unnecessary.

Characteristic equations

Representative equations are:

P_{dc,cmd} = P_{ref} + 2(v_{dc} - V_{dc,ref})\,\mathrm{regulate}_{vdc}

Q_{cmd} = Q_{ref}\,\mathrm{regulate}_q

i_{d,cmd} = \frac{2}{3}\frac{Q_{cmd,pu}}{V_{pk}}

i_{q,cmd} = \frac{2}{3}\frac{P_{ac,cmd,pu}}{V_{pk}}

i_A = i_{d,cmd}\cos\theta + i_{q,cmd}\sin\theta

v_{dc} i_{dc} + P_{dc,cmd,pu} = 0

P = v_A i_A + v_B i_B + v_C i_C

Q = \frac{1}{\sqrt{3}}\left((v_A-v_B)i_C + (v_B-v_C)i_A + (v_C-v_A)i_B\right)

Interface table

Category

Name

Meaning

Units

Input

v_A

Instantaneous phase-A AC terminal voltage

pu

Input

v_B

Instantaneous phase-B AC terminal voltage

pu

Input

v_C

Instantaneous phase-C AC terminal voltage

pu

Input

v_dc

DC bus voltage applied to the converter model

pu

Output

i_A

Injected phase-A current sent to the AC network

pu

Output

i_B

Injected phase-B current sent to the AC network

pu

Output

i_C

Injected phase-C current sent to the AC network

pu

Output

i_dc

DC current implied by the converter active-power balance

pu

Variable

theta

Internal synchronous angle used to synthesize abc current references

rad

Variable

P_ref

Active-power reference used by the averaged converter logic

system-base power

Variable

Q_ref

Reactive-power reference used by the averaged converter logic

system-base power

Variable

Vdc_ref

DC-voltage reference used when DC-voltage regulation is active

pu

Variable

i_A

Algebraic phase-A output current variable

pu

Variable

i_B

Algebraic phase-B output current variable

pu

Variable

i_C

Algebraic phase-C output current variable

pu

Variable

i_dc

Algebraic DC current variable

pu

Variable

P

Measured instantaneous active power at the AC interface

pu or system-base power

Variable

Q

Measured instantaneous reactive power at the AC interface

pu or system-base power

Parameter

P_loss

Converter loss term added on top of transferred active power

system-base power

Parameter

P0

Scheduled base active-power seed used by the control-reference resolver

system-base power

Parameter

omega_base

Base angular frequency used to evolve the internal synchronous angle

rad/s

Parameter

sbase

System base power used to normalize power commands

MVA or system-base power

Parameter

control1

First control mode selector

code

Parameter

control2

Second control mode selector

code

Parameter

control1_val

Target value associated with the first control mode

mode-dependent

Parameter

control2_val

Target value associated with the second control mode

mode-dependent

Parameter

phi_v

Initial AC voltage angle reference coming from the PF/EMT bridge

rad

Parameter

Vpk

Initial AC peak voltage magnitude used for current synthesis and initialization

pu

Parameter

Vdc_nom

Nominal DC voltage used by the control-reference resolver

pu

How to use it

  • Use it for simple EMT converter studies where only averaged current injection is required.

  • Do not use it when switching harmonics or detailed converter hardware effects matter.