J. MartΓ­ frequency-dependent EMT line

J. MartΓ­ frequency-dependent EMT line represents passive network physics through resistance, inductance, capacitance, coupling, or switching topology. Its equations enforce voltage-current constitutive relations and therefore affect energy storage, damping, propagation, fault current, or grounding behavior.

Typical use

  • Use it to reproduce the electrical path between sources, converters, machines, and loads.

  • Keep phases, terminal orientation, connection type, and SI/per-unit parameter bases consistent.

The J. MartΓ­ line is a travelling-wave transmission-line model with frequency-dependent modal propagation and characteristic admittance. It fits rational functions to sampled line data and uses those fitted poles and residues during the EMT simulation.

Model workflow

  1. Obtain frequency samples automatically from the line and its assigned tower or underground-cable template, or import compatible samples from an NPZ file.

  2. Transform the phase-domain samples to modal coordinates.

  3. Fit the characteristic admittance and propagation terms with vector fitting.

  4. Apply optional passivity checks and correction settings.

  5. Store the resulting runtime bundle on the symbolic line block.

Characteristic relations

In the frequency domain, terminal currents are related to terminal voltages by the fitted characteristic admittance Y_c(s) and propagation operator H(s):

I_f(s) = Y_c(s)V_f(s) - H(s)I_t(s)

I_t(s) = Y_c(s)V_t(s) - H(s)I_f(s)

Special settings

The Special settings tab contains the complete former creation-dialogue configuration: phases, sample source, nominal and sweep frequencies, imported sample path, vector-fitting orders and tolerances, iteration limits, weighting, stability enforcement, delay handling, and passivity tolerances. Applying the dialogue reconstructs the model from these values.

Interface table

Category

Name

Meaning

Units

Input

vf_X

From-terminal phase voltage

V or p.u.

Input

vt_X

To-terminal phase voltage

V or p.u.

Output

net_conn_if_X

From-terminal network current

A or p.u.

Output

net_conn_it_X

To-terminal network current

A or p.u.

The default topology is ABC without neutral. Enable neutral only when the connected network and line data both provide a neutral conductor.