PI lineο
PI line represents passive network physics through resistance, inductance, capacitance, coupling, or switching topology. Its equations enforce voltage-current constitutive relations and therefore affect energy storage, damping, propagation, fault current, or grounding behavior.
Typical useο
Use it to reproduce the electrical path between sources, converters, machines, and loads.
Keep phases, terminal orientation, connection type, and SI/per-unit parameter bases consistent.
This model represents a conductor-selective pi-section transmission line for EMT studies. It can retain any configured subset of the full NABC conductor set, so ABC is a common case rather than a restriction.
Purposeο
It is a phase-selective EMT pi-line model with explicit mapped R, L, and C parameter matrices.
Behaviorο
Uses active from-side and to-side terminal voltages as inputs.
Evolves series-current and shunt-charge-related dynamic variables.
Computes branch-port currents on both ends.
Reduces the full NABC parameter matrices to the physically active phase set.
Creates terminal ports and states only for enabled neutral and phase conductors; examples include A, AB, AC, ABC, NA, NAB, and NABC.
Characteristicsο
EMT branch model based on a pi equivalent.
Suitable for detailed phase-domain line studies.
More detailed than the RMS line power-flow-style template.
Interface tableο
Category |
Name |
Meaning |
Units |
|---|---|---|---|
Input |
|
From-side neutral terminal voltage when the neutral is active |
pu |
Input |
|
From-side phase-A terminal voltage when phase A is active |
pu |
Input |
|
From-side phase-B terminal voltage when phase B is active |
pu |
Input |
|
From-side phase-C terminal voltage when phase C is active |
pu |
Input |
|
To-side neutral terminal voltage when the neutral is active |
pu |
Input |
|
To-side phase-A terminal voltage when phase A is active |
pu |
Input |
|
To-side phase-B terminal voltage when phase B is active |
pu |
Input |
|
To-side phase-C terminal voltage when phase C is active |
pu |
Output |
|
From-side neutral current when the neutral is active |
pu |
Output |
|
From-side phase-A current when phase A is active |
pu |
Output |
|
From-side phase-B current when phase B is active |
pu |
Output |
|
From-side phase-C current when phase C is active |
pu |
Output |
|
To-side neutral current when the neutral is active |
pu |
Output |
|
To-side phase-A current when phase A is active |
pu |
Output |
|
To-side phase-B current when phase B is active |
pu |
Output |
|
To-side phase-C current when phase C is active |
pu |
Variable |
|
Series-current state for each active conductor |
pu |
Variable |
|
From-side shunt-charge state for each active conductor |
puΒ·s equivalent state |
Variable |
|
To-side shunt-charge state for each active conductor |
puΒ·s equivalent state |
Variable |
|
From-side shunt-capacitor current variable for each active conductor |
pu |
Variable |
|
To-side shunt-capacitor current variable for each active conductor |
pu |
Variable |
|
From-side branch-port current variable for each active conductor |
pu |
Variable |
|
To-side branch-port current variable for each active conductor |
pu |
Parameter |
|
Full NABC resistance matrix entries mapped from the line data |
pu |
Parameter |
|
Full NABC inverse-inductance matrix entries mapped from the line data |
1/(puΒ·s) |
Parameter |
|
Full NABC shunt-capacitance matrix entries mapped from the line data |
puΒ·s |
How to use itο
Use this template for phase-domain EMT line studies when a pi-equivalent representation is sufficient.
Use Bergeron or JMARTI-style alternatives when propagation-delay behavior is more important.