PV plant grid followingο
PV plant grid following represents an energy resource and its interface controls. Storage and photovoltaic models combine source-side energy or power limits with converter commands, so available active power, DC voltage, and reactive-power control must remain mutually consistent.
Typical useο
Use it to study renewable or storage response to voltage, frequency, and power-reference disturbances.
Respect energy, current, DC-voltage, and active/reactive capability limits during initialization.
This model represents a grid-following PV plant in EMT form.
Purposeο
It is the EMT PV plant template used when the photovoltaic resource must synchronize to an existing grid angle and inject controlled current into the network.
Behaviorο
Uses instantaneous three-phase terminal voltages as network inputs.
Computes the available active power from solar-resource-related quantities.
Applies MPPT-related logic to determine the active-power command.
Uses a PLL to estimate the grid angle and frequency.
Generates d-axis and q-axis current references through outer-loop control.
Produces phase currents injected into the EMT network through the embedded converter block.
Characteristicsο
EMT averaged grid-following plant model.
Includes PV availability logic, PLL synchronization, and current-control structure.
Appropriate for converter-dominated transient studies at the waveform timescale.
How it worksο
The plant first determines how much active power is physically available from the PV resource. That command is filtered or limited through MPPT-related logic. A PLL then aligns the controller with the grid voltage. Outer control loops convert active-power and reactive-power objectives into dq current references, and the converter block turns those references into three-phase current injection.
Characteristic equationsο
Interface tableο
Category |
Name |
Meaning |
Units |
|---|---|---|---|
Input |
|
Instantaneous phase-A AC terminal voltage seen by the PV converter |
pu |
Input |
|
Instantaneous phase-B AC terminal voltage seen by the PV converter |
pu |
Input |
|
Instantaneous phase-C AC terminal voltage seen by the PV converter |
pu |
Output |
|
Phase-A current injected by the PV plant into the EMT network |
pu |
Output |
|
Phase-B current injected by the PV plant into the EMT network |
pu |
Output |
|
Phase-C current injected by the PV plant into the EMT network |
pu |
Variable |
|
Active-power availability computed from irradiance, temperature, and PV-side limits |
pu |
Variable |
|
Active-power command produced by the MPPT-related logic before converter limits are applied |
pu |
Variable |
|
Internal DC-link voltage of the imported averaged VSC block |
pu |
Variable |
|
Internal PLL phase angle used by the grid-following converter controls |
rad |
Variable |
|
Internal PLL frequency estimate used by the grid-following converter controls |
pu |
Variable |
|
d-axis current reference generated by the outer active-power or DC-voltage control loop |
pu |
Variable |
|
q-axis current reference generated by the outer reactive-power or voltage-related control loop |
pu |
Parameter |
|
Solar irradiance input used by the PV availability model |
W/m^2 |
Parameter |
|
PV cell temperature used by the PV availability model |
degC |
Parameter |
|
Rated active power of the PV plant model |
pu |
Parameter |
|
Base electrical angular frequency used by the imported converter controls |
rad/s |
Parameter |
|
Proportional gain of the imported PLL controller |
pu/pu |
Parameter |
|
Integral gain of the imported PLL controller |
pu/(pu s) |
How to use itο
Use it when one PV plant must follow the existing network angle and inject controlled current into an EMT network.
Do not use it as a grid-forming resource; use the grid-forming converter family instead when the source must establish its own voltage angle.