PV plant grid following

PV plant grid following represents an energy resource and its interface controls. Storage and photovoltaic models combine source-side energy or power limits with converter commands, so available active power, DC voltage, and reactive-power control must remain mutually consistent.

Typical use

  • Use it to study renewable or storage response to voltage, frequency, and power-reference disturbances.

  • Respect energy, current, DC-voltage, and active/reactive capability limits during initialization.

This model represents a grid-following PV plant in EMT form.

Purpose

It is the EMT PV plant template used when the photovoltaic resource must synchronize to an existing grid angle and inject controlled current into the network.

Behavior

  • Uses instantaneous three-phase terminal voltages as network inputs.

  • Computes the available active power from solar-resource-related quantities.

  • Applies MPPT-related logic to determine the active-power command.

  • Uses a PLL to estimate the grid angle and frequency.

  • Generates d-axis and q-axis current references through outer-loop control.

  • Produces phase currents injected into the EMT network through the embedded converter block.

Characteristics

  • EMT averaged grid-following plant model.

  • Includes PV availability logic, PLL synchronization, and current-control structure.

  • Appropriate for converter-dominated transient studies at the waveform timescale.

How it works

The plant first determines how much active power is physically available from the PV resource. That command is filtered or limited through MPPT-related logic. A PLL then aligns the controller with the grid voltage. Outer control loops convert active-power and reactive-power objectives into dq current references, and the converter block turns those references into three-phase current injection.

Characteristic equations

P_{avail} = f(\text{irradiance}, \text{temperature})

\omega_{pll} = K_p e_{pll} + K_i \int e_{pll}\,dt

\frac{d\theta_{pll}}{dt} = \omega_{base}(\omega_{pll}-1)

\{i_A, i_B, i_C\} = T_{dq0 \rightarrow abc}(i_d^{ref}, i_q^{ref}, \theta_{pll})

Interface table

Category

Name

Meaning

Units

Input

v_A

Instantaneous phase-A AC terminal voltage seen by the PV converter

pu

Input

v_B

Instantaneous phase-B AC terminal voltage seen by the PV converter

pu

Input

v_C

Instantaneous phase-C AC terminal voltage seen by the PV converter

pu

Output

i_A

Phase-A current injected by the PV plant into the EMT network

pu

Output

i_B

Phase-B current injected by the PV plant into the EMT network

pu

Output

i_C

Phase-C current injected by the PV plant into the EMT network

pu

Variable

P_avail

Active-power availability computed from irradiance, temperature, and PV-side limits

pu

Variable

P_mppt

Active-power command produced by the MPPT-related logic before converter limits are applied

pu

Variable

vdc

Internal DC-link voltage of the imported averaged VSC block

pu

Variable

theta_pll

Internal PLL phase angle used by the grid-following converter controls

rad

Variable

omega_pll

Internal PLL frequency estimate used by the grid-following converter controls

pu

Variable

i_d_ref

d-axis current reference generated by the outer active-power or DC-voltage control loop

pu

Variable

i_q_ref

q-axis current reference generated by the outer reactive-power or voltage-related control loop

pu

Parameter

irradiance

Solar irradiance input used by the PV availability model

W/m^2

Parameter

temperature

PV cell temperature used by the PV availability model

degC

Parameter

P_rated

Rated active power of the PV plant model

pu

Parameter

omega_base

Base electrical angular frequency used by the imported converter controls

rad/s

Parameter

k_p_pll

Proportional gain of the imported PLL controller

pu/pu

Parameter

k_i_pll

Integral gain of the imported PLL controller

pu/(pu s)

How to use it

  • Use it when one PV plant must follow the existing network angle and inject controlled current into an EMT network.

  • Do not use it as a grid-forming resource; use the grid-forming converter family instead when the source must establish its own voltage angle.