Sauer-Pai generator

Sauer-Pai generator belongs to an electromechanical machine or prime-mover model. It links electrical torque and flux with rotor speed, angle, mechanical power, or actuator dynamics, making it central to frequency, voltage, and rotor-angle stability studies.

Typical use

  • Use it when electrical transients must interact with rotating mass or machine controls.

  • Initialize torque, power, flux, and speed consistently with the solved power flow.

This model represents the Sauer-Pai synchronous machine block used within the EMT complete generator model.

Purpose

It is the phase-domain synchronous-machine EMT model built by get_generator_sauer_pai_type_emt_template().

Behavior

  • Receives three-phase terminal voltages from the wrapper.

  • Receives mechanical torque from the governor and field voltage from the exciter.

  • Evolves electromagnetic, mechanical, and zero-sequence states.

  • Injects phase currents into the network and exports torque, speed, and exciter feedback channels.

Characteristics

  • EMT abc-domain machine model.

  • Includes Park-transform-based dq0 dynamics internally.

  • Includes explicit zero-sequence dynamics.

  • Includes transient and subtransient magnetic states.

Characteristic equations

\frac{d\theta_{abs}}{dt} = \omega_b \omega

\frac{d\omega}{dt} = \frac{T_m - T_e - D(\omega - \omega_s)}{2H}

\frac{d\psi_d}{dt} = \omega_b (r_a i_d + \omega \psi_q + v_d)

\frac{d\psi_q}{dt} = \omega_b (r_a i_q - \omega \psi_d + v_q)

\frac{d\psi_0}{dt} = \omega_b (r_a i_0 + v_0)

\frac{de_{qp}}{dt} = \frac{-I_{RPu} + v_f}{T_{d0p}}

0 = \psi_d + x_{dpp} i_d - \gamma_{d1} e_{qp} - (1-\gamma_{d1})\psi_{pp,d}

0 = \psi_q + x_{qpp} i_q + \gamma_{q1} e_{dp} - (1-\gamma_{q1})\psi_{pp,q}

0 = \psi_0 + x_0 i_0

Interface table

Category

Name

Meaning

Units

Input

v_A

Instantaneous phase-A terminal voltage

pu

Input

v_B

Instantaneous phase-B terminal voltage

pu

Input

v_C

Instantaneous phase-C terminal voltage

pu

Input

Tm

Mechanical torque input from the governor

pu

Input

v_f

Field-voltage input from the exciter

pu

Output

i_A

Phase-A current injected into the EMT network

pu

Output

i_B

Phase-B current injected into the EMT network

pu

Output

i_C

Phase-C current injected into the EMT network

pu

Output

omega

Rotor speed shared with the governor and stabilizer

pu

Output

IRPu

Exciter feedback quantity exported to the exciter block

pu

Output

Te

Electromagnetic torque exported to the composite generator chain

pu

Variable

theta_abs

Absolute electrical rotor angle used by the EMT Park transform

rad

Variable

omega

Rotor speed state

pu

Variable

psi_d

d-axis flux state

pu

Variable

psi_q

q-axis flux state

pu

Variable

psi_0

zero-sequence flux state

pu

Variable

e_qp

q-axis transient emf state

pu

Variable

e_dp

d-axis transient emf state

pu

Variable

psi_pp_d

d-axis subtransient flux state

pu

Variable

psi_pp_q

q-axis subtransient flux state

pu

Variable

v_d

d-axis internal voltage after abc-to-dq0 transformation

pu

Variable

v_q

q-axis internal voltage after abc-to-dq0 transformation

pu

Variable

v_0

zero-sequence internal voltage

pu

Variable

i_d

d-axis current

pu

Variable

i_q

q-axis current

pu

Variable

i_0

zero-sequence current

pu

Variable

i_A

Algebraic phase-A current output variable

pu

Variable

i_B

Algebraic phase-B current output variable

pu

Variable

i_C

Algebraic phase-C current output variable

pu

Variable

Te

Electromagnetic torque variable

pu

Variable

p_e

Instantaneous three-phase electrical active power

pu

Variable

q_e

Instantaneous three-phase electrical reactive power

pu

Variable

IRPu

Exciter feedback quantity derived from the q-axis emf channel

pu

Parameter

ra

Armature resistance

pu

Parameter

xd

d-axis synchronous reactance

pu

Parameter

xq

q-axis synchronous reactance

pu

Parameter

xdp

d-axis transient reactance

pu

Parameter

xqp

q-axis transient reactance

pu

Parameter

xdpp

d-axis subtransient reactance

pu

Parameter

xqpp

q-axis subtransient reactance

pu

Parameter

xl

Leakage reactance

pu

Parameter

x0

zero-sequence reactance

pu

Parameter

Td0p

d-axis open-circuit transient time constant

s

Parameter

Tq0p

q-axis open-circuit transient time constant

s

Parameter

Td0pp

d-axis open-circuit subtransient time constant

s

Parameter

Tq0pp

q-axis open-circuit subtransient time constant

s

Parameter

gamma_d1

d-axis magnetic coupling coefficient

pu

Parameter

gamma_q1

q-axis magnetic coupling coefficient

pu

Parameter

gamma_d2

d-axis magnetic coupling coefficient used in the Sauer-Pai equations

pu

Parameter

gamma_q2

q-axis magnetic coupling coefficient used in the Sauer-Pai equations

pu

Parameter

H

Inertia constant

s

Parameter

D

Damping coefficient

pu-based model constant

Parameter

omega_b

Base electrical angular frequency

rad/s

Parameter

omega_s

Synchronous reference speed used by the swing equation

pu

How to use it

  • Treat this as the machine core of the packaged EMT Complete generator model.

  • Use the higher-level Complete generator document when you want the full governor-exciter-stabilizer-machine assembly.