Shunt C

Shunt C represents a capacitive shunt connected between one or more phase conductors and a reference point. It retains capacitor-voltage or charge dynamics and supplies capacitive reactive current according to the instantaneous terminal voltage.

Typical use

  • Use it for capacitor banks, filters, cable or equipment shunt capacitance, and the capacitive part of a parallel RLC equivalent.

  • Configure the actual active conductors and connection; ABC is only one possible interface.

The template accepts any non-empty subset of phases A, B, and C and can expose a neutral for the appropriate star connection. It therefore supports single-, two-, and three-phase arrangements such as A, AB, AC, BC, ABC and applicable neutral-inclusive variants such as NA, NAB, NAC, NBC, and NABC.

Electrical model

For an enabled star branch X,

v_{C,X}=v_X-v_N,

i_{C,X}=C_X\frac{d v_{C,X}}{dt}.

The stored electric energy is

W_{C,X}=\frac{1}{2}C_Xv_{C,X}^2.

The external current follows VeraGrid’s network-injection sign convention. Delta branches use the line-to-line voltage of each enabled pair.

Phase and neutral configurations

Connection

Electrical reference

Neutral port

Notes

Grounded star

Ground

No external neutral is needed

One independent capacitor is created for every enabled phase.

Neutral star

External neutral conductor

Yes

Neutral current balances the enabled phase currents.

Floating star

Internal star point

No

The internal neutral voltage is solved from current balance.

Delta

Other enabled phase conductors

No

At least two phases are required; capacitors are placed between active pairs.

Only enabled conductors, variables, equations, and mappings are created.

Parameter sources

For a star-connected equivalent, each phase capacitance can be obtained from nominal capacitive reactive power:

C_X=\frac{Q_{l0,X}}{V_{nom}^2\,\omega_{base}}.

Delta equivalents use explicit line-to-line branch capacitances. Check the reactive-power sign convention and whether the source quantity is per-phase or total before mapping it.

Interface table

The symbol X denotes an enabled phase and XY an enabled delta pair.

Category

Name

Meaning

Units

Input

v_X

Instantaneous voltage of enabled phase X

pu

Input

v_N

Instantaneous neutral voltage for a neutral-star interface

pu

Output

i_X

Current injected into the network at enabled phase X

pu

Output

i_N

Neutral current injection when an external neutral is present

pu

Variable

v_C_X

Capacitor voltage of star branch X

pu

Variable

v_C_XY

Capacitor voltage of delta branch XY

pu

Parameter

C_X

Star-branch capacitance for phase X

puΒ·s

Parameter

C_XY

Delta capacitance between enabled phases X and Y

puΒ·s

Parameter

Ql0_X

Initial capacitive reactive power used to derive C_X

pu

Parameter

Vnom

Nominal voltage used for parameter conversion

pu

Parameter

omega_base

Base electrical angular frequency

rad/s

Initialization and numerical limits

The initial capacitor voltage must agree with the initialized terminal voltages and connection. Inconsistent values cause an artificial charging transient. Capacitance must be positive. Very small capacitance can introduce fast transients, while very large capacitance can dominate the network energy and slow the response. A zero reactive-power mapping needs explicit handling rather than relying on a singular parameter conversion.

How to use it

  1. Enable the physical phase and neutral conductors.

  2. Select the correct grounded-star, neutral-star, floating-star, or delta connection.

  3. Map the initial capacitive reactive power or supply explicit branch capacitances.

  4. Check the initial capacitor voltages and reactive-power sign.

  5. Select an EMT time step that resolves the fastest network resonance involving this capacitance.