Shunt L

Shunt L represents an inductive shunt connected between one or more phase conductors and a reference point. Unlike a static reactive-power load, it retains the electromagnetic current state of every enabled branch.

Typical use

  • Use it for shunt reactors, magnetizing equivalents, and the inductive part of a parallel RLC load.

  • Select the actual conductors and connection instead of assuming a balanced ABC device.

The template accepts any non-empty subset of phases A, B, and C. Depending on the selected star connection, it can also expose a neutral conductor. It therefore covers A, AB, AC, BC, ABC and their applicable neutral-inclusive forms, including NA, NAB, NAC, NBC, and NABC.

Electrical model

For an enabled star branch X, the absorbed branch current obeys

L_X\frac{d i_{L,X}}{dt}=v_X-v_N.

The corresponding stored magnetic energy is

W_{L,X}=\frac{1}{2}L_X i_{L,X}^2.

External port currents use VeraGrid’s network-injection convention and are therefore opposite to absorbed load current. Delta branches use line-to-line voltages, such as v_A-v_B, and one current state per active phase pair.

Phase and neutral configurations

Connection

Electrical reference

Neutral port

Notes

Grounded star

Ground

No external neutral is needed

Each enabled phase has an independent inductor to ground.

Neutral star

External neutral conductor

Yes

The neutral carries the sum of the enabled phase branch currents.

Floating star

Internal star point

No

The star-point voltage is solved while enforcing zero current sum.

Delta

Other enabled phase conductors

No

At least two phases are required; a state is created for each active pair.

Only selected conductors appear at the external interface. ABC is a common configuration, not a limitation of the template.

Parameter sources

For a star-connected load equivalent, each phase inductance can be obtained from its nominal reactive-power demand:

L_X=\frac{V_{nom}^2}{Q_{l0,X}\,\omega_{base}}.

Delta equivalents use explicit line-to-line branch inductances. Verify whether the source data represents total three-phase power or per-phase power before mapping it.

Interface table

The symbol X denotes an enabled phase and XY an enabled delta pair.

Category

Name

Meaning

Units

Input

v_X

Instantaneous voltage of enabled phase X

pu

Input

v_N

Instantaneous neutral voltage for a neutral-star interface

pu

Output

i_X

Current injected into the network at enabled phase X

pu

Output

i_N

Neutral current injection when an external neutral is present

pu

State

i_L_X

Current state of star branch X

pu

State

i_L_XY

Current state of delta branch XY

pu

Parameter

L_X

Star-branch inductance for phase X

puΒ·s

Parameter

L_XY

Delta inductance between enabled phases X and Y

puΒ·s

Parameter

Ql0_X

Initial inductive reactive power used to derive L_X

pu

Parameter

Vnom

Nominal voltage used for parameter conversion

pu

Parameter

omega_base

Base electrical angular frequency

rad/s

Initialization and numerical limits

Branch currents are initialized from the steady operating point. The initial currents, phase voltages, connection, and reactive-power sign must describe the same physical state; otherwise an artificial transient appears at the first time step. Inductance must be positive. Very small inductances create a fast electrical time scale and may require a smaller EMT step, while a zero reactive-power mapping must not be allowed to create an infinite or undefined parameter.

How to use it

  1. Enable the required phases and neutral conductor.

  2. Choose the physical star or delta connection.

  3. Map the initial reactive load or supply explicit inductances.

  4. Verify the initialized branch currents and reactive-power sign.

  5. Reduce the EMT time step if the chosen inductance produces dynamics faster than the existing step can resolve.