Thevenin generatorο
Thevenin generator imposes or controls an electrical excitation in an EMT network. Depending on the variant, it prescribes voltage or current directly or through a source-equivalent impedance. It is used to represent the grid, a controlled converter terminal, or a standardized transient waveform.
Typical useο
Use it as a network boundary, disturbance source, or controlled electrical terminal.
Match polarity, phase convention, grounding, and source impedance to the connected topology.
This model represents a Thevenin-equivalent generator source for EMT studies.
Purposeο
It is a three-phase Thevenin-equivalent EMT generator with RL current dynamics and an internally reconstructed balanced emf.
Behaviorο
Uses three-phase terminal voltages as inputs.
Evolves three phase-current states and one electrical-angle state.
Reconstructs the internal balanced emf from power-flow-derived initialization quantities.
Injects abc currents into the EMT network according to a source-behind-impedance structure.
Characteristicsο
Compact EMT source model.
Useful when a full synchronous machine and controls are not required.
Supports higher-level shared-reference wiring without changing the local source equations.
Characteristic equationsο
Equivalent Β±2Ο/3 phase shifts are used for e_B and e_C.
Interface tableο
Category |
Name |
Meaning |
Units |
|---|---|---|---|
Input |
|
Instantaneous phase-A terminal voltage |
pu |
Input |
|
Instantaneous phase-B terminal voltage |
pu |
Input |
|
Instantaneous phase-C terminal voltage |
pu |
Output |
|
Phase-A current injected into the EMT network |
pu |
Output |
|
Phase-B current injected into the EMT network |
pu |
Output |
|
Phase-C current injected into the EMT network |
pu |
Variable |
|
Phase-A current state variable |
pu |
Variable |
|
Phase-B current state variable |
pu |
Variable |
|
Phase-C current state variable |
pu |
Variable |
|
Internal electrical angle of the balanced source |
rad |
Variable |
|
Internal phase-A emf |
pu |
Variable |
|
Internal phase-B emf |
pu |
Variable |
|
Internal phase-C emf |
pu |
Variable |
|
Instantaneous electrical active power measured at the source terminals |
pu |
Variable |
|
Instantaneous electrical reactive power measured at the source terminals |
pu |
Parameter |
|
Base electrical angular frequency |
rad/s |
Parameter |
|
Source resistance |
pu |
Parameter |
|
Source reactance |
pu |
Parameter |
|
Power-flow-derived terminal voltage angle used for initialization |
rad |
Parameter |
|
Power-flow-derived current-to-voltage phase relation used for initialization |
rad |
Parameter |
|
Power-flow-derived peak phase-voltage magnitude used for initialization |
pu |
Parameter |
|
Power-flow-derived peak phase-current magnitude used for initialization |
pu |
Parameter |
|
Runtime angle-deviation offset applied to the internal emf |
rad |
Parameter |
|
Runtime frequency scaling applied to the angle state equation |
pu |
Parameter |
|
Runtime emf-magnitude scaling factor |
pu |
Parameter |
|
Higher-level flag used by orchestration logic for shared-reference behavior |
0/1 |
Parameter |
|
Higher-level active-power sharing reference |
pu |
Parameter |
|
Higher-level reactive-power sharing reference |
pu |
How to use itο
Use this template when you want a compact EMT source behind impedance.
Use the EMT
Complete generatorinstead when you need explicit machine, exciter, governor, and stabilizer dynamics.