Transformerο
Transformer represents passive network physics through resistance, inductance, capacitance, coupling, or switching topology. Its equations enforce voltage-current constitutive relations and therefore affect energy storage, damping, propagation, fault current, or grounding behavior.
Typical useο
Use it to reproduce the electrical path between sources, converters, machines, and loads.
Keep phases, terminal orientation, connection type, and SI/per-unit parameter bases consistent.
This model represents a three-phase transformer for EMT studies.
Purposeο
It is the EMT transformer used to exchange instantaneous three-phase voltages and currents between two electrical sides while preserving winding dynamics, magnetic coupling, and the chosen connection structure.
Behaviorο
Uses phase voltages at both transformer terminals and, when available, neutral-node voltages.
Evolves internal winding currents dynamically.
Produces current injections at both sides of the transformer.
Represents resistive losses, leakage effects, magnetic coupling, and off-nominal tap scaling.
Characteristicsο
EMT three-phase transformer model.
Appropriate for phase-domain transient simulations.
Supports neutral-related behavior when the chosen winding connection exposes neutral ports.
How it worksο
The transformer is represented through coupled winding equations. The terminal voltages drive winding currents, the winding currents interact through mutual inductance, and the resulting current states are exported back to the EMT network as current injections. Compared with the RMS transformer, this block preserves fast electromagnetic dynamics and phase-domain behavior.
Characteristic equationsο
Representative winding equations are:
The exact equations depend on the chosen winding arrangement, tap ratio, and neutral exposure.
Interface tableο
Category |
Name |
Meaning |
Units |
|---|---|---|---|
Input |
|
From-side phase-A terminal voltage applied to the transformer |
pu |
Input |
|
From-side phase-B terminal voltage applied to the transformer |
pu |
Input |
|
From-side phase-C terminal voltage applied to the transformer |
pu |
Input |
|
To-side phase-A terminal voltage applied to the transformer |
pu |
Input |
|
To-side phase-B terminal voltage applied to the transformer |
pu |
Input |
|
To-side phase-C terminal voltage applied to the transformer |
pu |
Input |
|
From-side neutral voltage when the selected winding connection exposes a neutral port |
pu |
Input |
|
To-side neutral voltage when the selected winding connection exposes a neutral port |
pu |
Output |
|
Current injected by the transformer at the from-side phase-A port |
pu |
Output |
|
Current injected by the transformer at the from-side phase-B port |
pu |
Output |
|
Current injected by the transformer at the from-side phase-C port |
pu |
Output |
|
Current injected by the transformer at the to-side phase-A port |
pu |
Output |
|
Current injected by the transformer at the to-side phase-B port |
pu |
Output |
|
Current injected by the transformer at the to-side phase-C port |
pu |
Output |
|
Current injected at the from-side neutral port when a grounded-star connection is present |
pu |
Output |
|
Current injected at the to-side neutral port when a grounded-star connection is present |
pu |
Variable |
|
Internal from-side winding current state associated with phase A |
pu |
Variable |
|
Internal from-side winding current state associated with phase B |
pu |
Variable |
|
Internal from-side winding current state associated with phase C |
pu |
Variable |
|
Internal to-side winding current state associated with phase A |
pu |
Variable |
|
Internal to-side winding current state associated with phase B |
pu |
Variable |
|
Internal to-side winding current state associated with phase C |
pu |
Variable |
|
Exported from-side phase-A port current derived from the winding states |
pu |
Variable |
|
Exported from-side phase-B port current derived from the winding states |
pu |
Variable |
|
Exported from-side phase-C port current derived from the winding states |
pu |
Variable |
|
Exported to-side phase-A port current derived from the winding states |
pu |
Variable |
|
Exported to-side phase-B port current derived from the winding states |
pu |
Variable |
|
Exported to-side phase-C port current derived from the winding states |
pu |
Parameter |
|
Resistance of the from-side winding |
pu |
Parameter |
|
Resistance of the to-side winding |
pu |
Parameter |
|
Leakage inductance of the from-side winding |
pu s |
Parameter |
|
Leakage inductance of the to-side winding |
pu s |
Parameter |
|
Mutual inductance coupling the two windings |
pu s |
Parameter |
|
Magnetizing conductance or core-loss branch parameter |
pu |
Parameter |
|
Off-nominal tap ratio applied between the two windings |
pu |
How to use itο
Use it for EMT simulations that need phase-domain transformer current and voltage behavior.
Prefer the RMS transformer only when high-frequency electromagnetic detail is unnecessary.