VSC Grid-Forming (GFM)ο
VSC Grid-Forming (GFM) represents a power-electronic conversion or modulation function. Converter models translate control references into AC/DC electrical quantities, while averaged and switched variants retain different levels of switching detail and therefore require different simulation time steps.
Typical useο
Use averaged models for control and system studies, and switched models when waveform detail matters.
Coordinate reference frames, modulation limits, DC-side energy, and current-control bandwidth.
This model represents a grid-forming voltage-source converter in EMT form.
Purposeο
It is the EMT grid-forming converter template used when the converter must establish its own voltage angle and magnitude instead of locking to an external grid reference.
Behaviorο
Uses three-phase terminal voltages and one DC-side voltage input.
Maintains an internal electrical angle and frequency.
Synthesizes an internal balanced three-phase emf behind a series output branch.
Measures active and reactive power at the AC interface.
Adjusts frequency and voltage magnitude through droop control.
Produces AC current injections and one implied DC current channel.
Characteristicsο
EMT grid-forming converter model.
Source-behind-impedance representation.
Suitable for islanded systems, weak-grid studies, and converter-dominated systems where the converter sets the local voltage reference.
How it worksο
The converter behaves like a controlled internal three-phase source behind an output impedance. Its internal angle evolves from a frequency state, and that frequency is adjusted from active-power error through droop control. The internal emf magnitude is adjusted from reactive-power error through voltage droop. The branch impedance then determines the current exchanged with the network.
Characteristic equationsο
Interface tableο
Category |
Name |
Meaning |
Units |
|---|---|---|---|
Input |
|
Instantaneous phase-A AC terminal voltage applied to the converter output branch |
pu |
Input |
|
Instantaneous phase-B AC terminal voltage applied to the converter output branch |
pu |
Input |
|
Instantaneous phase-C AC terminal voltage applied to the converter output branch |
pu |
Input |
|
DC terminal voltage used to compute DC power balance |
pu |
Output |
|
Phase-A current injected by the grid-forming converter into the EMT network |
pu |
Output |
|
Phase-B current injected by the grid-forming converter into the EMT network |
pu |
Output |
|
Phase-C current injected by the grid-forming converter into the EMT network |
pu |
Output |
|
DC current implied by the converter active-power balance |
pu |
Variable |
|
Internal electrical angle of the converter voltage source |
rad |
Variable |
|
Internal per-unit electrical frequency after P-f droop control |
pu |
Variable |
|
Peak magnitude of the internal balanced three-phase emf |
pu |
Variable |
|
Internal phase-A emf behind the series RL branch |
pu |
Variable |
|
Internal phase-B emf behind the series RL branch |
pu |
Variable |
|
Internal phase-C emf behind the series RL branch |
pu |
Variable |
|
Instantaneous active power measured at the AC interface for frequency droop control |
pu |
Variable |
|
Instantaneous reactive power measured at the AC interface for voltage droop control |
pu |
Parameter |
|
Base electrical angular frequency used by the state equations |
rad/s |
Parameter |
|
Series resistance of the converter output branch |
pu |
Parameter |
|
Series reactance of the converter output branch |
pu |
Parameter |
|
Active-power-to-frequency droop gain |
pu frequency/pu power |
Parameter |
|
Reactive-power-to-voltage droop gain |
pu voltage/pu reactive power |
Parameter |
|
Time constant of the internal frequency-control state |
s |
Parameter |
|
Time constant of the internal voltage-magnitude-control state |
s |
Parameter |
|
Frequency reference used by the grid-forming droop controller |
pu |
Parameter |
|
Active-power reference used by the frequency droop controller |
pu |
Parameter |
|
Reactive-power reference used by the voltage droop controller |
pu |
Parameter |
|
Voltage-magnitude reference used by the voltage droop controller |
pu |
Parameter |
|
Initialization reactive-power quantity used by the EMT/PF bridge for this converter |
pu |
Parameter |
|
Initialization peak-voltage magnitude used to seed the internal emf state |
pu |
Parameter |
|
Initialization terminal-voltage angle used to seed the internal emf state |
rad |
Parameter |
|
Initialization peak-current magnitude used to align the EMT state with the solved operating point |
pu |
Parameter |
|
Initialization current-to-voltage phase relation used to align the EMT state with the solved operating point |
rad |
How to use itο
Use it when the converter must form the grid voltage rather than track it.
Do not replace a grid-following converter with this model unless the control philosophy of the study is truly grid-forming.