ZIP load

ZIP load describes how electrical demand responds to terminal voltage. Its constant-impedance, constant-current, and constant-power components produce different fault and recovery behavior, so their proportions materially change the simulated response.

Typical use

  • Use the formulation that matches the time scale and measured behavior of the represented demand.

  • Initialize active and reactive demand from the power flow and verify the voltage-dependence convention.

This model represents a phase-selective EMT ZIP load with per-phase voltage filtering and polynomial voltage dependence.

It is not restricted to ABC. Any non-empty subset of phases A, B, and C can be enabled. Star connections can use ground, an external neutral, or a floating internal star point; delta connections create branches between enabled phase pairs. Only active conductors create ports, states, equations, and mappings.

Purpose

It is a phase-selective EMT ZIP load with per-phase SOGI filtering and polynomial voltage dependence.

Behavior

  • Uses the active phase voltages as external inputs.

  • Filters each active phase voltage with internal SOGI states.

  • Computes per-phase active and reactive load behavior from ZIP coefficients.

  • Produces per-phase current injections accordingly.

Characteristics

  • Dynamic phase-domain load model.

  • Supports impedance/current/power blending through ZIP coefficients.

  • More realistic than a fixed load when voltage dependence matters.

Characteristic equations

For each active branch, let r_X=V_X/V_0 be the filtered voltage magnitude normalized by its reference. The ZIP laws are

P_X=P_{0,X}(a_1r_X^2+a_2r_X+a_3),

Q_X=Q_{0,X}(a_4r_X^2+a_5r_X+a_6).

The quadratic terms represent constant impedance, the linear terms constant current, and the constant terms constant power. The current injection is reconstructed from the filtered in-phase and quadrature voltage components with a regularized denominator.

For a pure component, the corresponding coefficient triplet normally sums to one. Mixed coefficients should be checked at r_X=1 so the model reproduces the nominal operating-point power.

Interface table

Category

Name

Meaning

Units

Input

v_A

Phase-A terminal voltage when phase A is active

pu

Input

v_B

Phase-B terminal voltage when phase B is active

pu

Input

v_C

Phase-C terminal voltage when phase C is active

pu

Output

i_A

Phase-A current injection when phase A is active

pu

Output

i_B

Phase-B current injection when phase B is active

pu

Output

i_C

Phase-C current injection when phase C is active

pu

Variable

u_phase

In-phase SOGI state for each active phase

pu

Variable

q_phase

Quadrature SOGI state for each active phase

pu

Variable

Vphase2

Squared filtered voltage magnitude variable for each active phase

pu^2

Variable

Vmphase

Filtered voltage magnitude variable for each active phase

pu

Variable

rphase

Normalized voltage ratio used by the ZIP polynomial for each active phase

pu

Variable

P_phase

Per-phase active load power variable

pu

Variable

Q_phase

Per-phase reactive load power variable

pu

Variable

i_phase

Per-phase output current variable

pu

Parameter

V0

Nominal voltage magnitude used by the ZIP law

pu

Parameter

a1

Constant-impedance active-power coefficient

pu

Parameter

a2

Constant-current active-power coefficient

pu

Parameter

a3

Constant-power active-power coefficient

pu

Parameter

a4

Constant-impedance reactive-power coefficient

pu

Parameter

a5

Constant-current reactive-power coefficient

pu

Parameter

a6

Constant-power reactive-power coefficient

pu

Parameter

k_sogi

SOGI filter gain

pu

Parameter

eps

Small numerical regularization constant

pu

Parameter

omega

Angular frequency used by the SOGI filter

rad/s

Parameter

P0_phase

Nominal per-phase active power setpoint

pu

Parameter

Q0_phase

Nominal per-phase reactive power setpoint

pu

The phase placeholder means each enabled star branch or active delta phase pair. The explicit A/B/C rows appear only when those conductors are selected; neutral ports appear only for a neutral-star configuration.

How to use it

  • Use this template when you need an EMT load whose power changes with terminal voltage.

  • It is especially useful when ZIP composition matters more than machine-type load dynamics.

  • Verify the initialized total power and injection sign after choosing phases and connection.

  • Retain a positive eps and inspect deep-fault behavior: regularization prevents singular current but does not define missing physical load-disconnection behavior.