ZIP loadο
ZIP load describes how electrical demand responds to terminal voltage. Its constant-impedance, constant-current, and constant-power components produce different fault and recovery behavior, so their proportions materially change the simulated response.
Typical useο
Use the formulation that matches the time scale and measured behavior of the represented demand.
Initialize active and reactive demand from the power flow and verify the voltage-dependence convention.
This model represents a phase-selective EMT ZIP load with per-phase voltage filtering and polynomial voltage dependence.
It is not restricted to ABC. Any non-empty subset of phases A, B, and C can be enabled. Star connections can use ground, an external neutral, or a floating internal star point; delta connections create branches between enabled phase pairs. Only active conductors create ports, states, equations, and mappings.
Purposeο
It is a phase-selective EMT ZIP load with per-phase SOGI filtering and polynomial voltage dependence.
Behaviorο
Uses the active phase voltages as external inputs.
Filters each active phase voltage with internal SOGI states.
Computes per-phase active and reactive load behavior from ZIP coefficients.
Produces per-phase current injections accordingly.
Characteristicsο
Dynamic phase-domain load model.
Supports impedance/current/power blending through ZIP coefficients.
More realistic than a fixed load when voltage dependence matters.
Characteristic equationsο
For each active branch, let be the filtered voltage magnitude normalized by its reference. The ZIP laws are
The quadratic terms represent constant impedance, the linear terms constant current, and the constant terms constant power. The current injection is reconstructed from the filtered in-phase and quadrature voltage components with a regularized denominator.
For a pure component, the corresponding coefficient triplet normally sums to one. Mixed coefficients should be checked at so the model reproduces the nominal operating-point power.
Interface tableο
Category |
Name |
Meaning |
Units |
|---|---|---|---|
Input |
|
Phase-A terminal voltage when phase A is active |
pu |
Input |
|
Phase-B terminal voltage when phase B is active |
pu |
Input |
|
Phase-C terminal voltage when phase C is active |
pu |
Output |
|
Phase-A current injection when phase A is active |
pu |
Output |
|
Phase-B current injection when phase B is active |
pu |
Output |
|
Phase-C current injection when phase C is active |
pu |
Variable |
|
In-phase SOGI state for each active phase |
pu |
Variable |
|
Quadrature SOGI state for each active phase |
pu |
Variable |
|
Squared filtered voltage magnitude variable for each active phase |
pu^2 |
Variable |
|
Filtered voltage magnitude variable for each active phase |
pu |
Variable |
|
Normalized voltage ratio used by the ZIP polynomial for each active phase |
pu |
Variable |
|
Per-phase active load power variable |
pu |
Variable |
|
Per-phase reactive load power variable |
pu |
Variable |
|
Per-phase output current variable |
pu |
Parameter |
|
Nominal voltage magnitude used by the ZIP law |
pu |
Parameter |
|
Constant-impedance active-power coefficient |
pu |
Parameter |
|
Constant-current active-power coefficient |
pu |
Parameter |
|
Constant-power active-power coefficient |
pu |
Parameter |
|
Constant-impedance reactive-power coefficient |
pu |
Parameter |
|
Constant-current reactive-power coefficient |
pu |
Parameter |
|
Constant-power reactive-power coefficient |
pu |
Parameter |
|
SOGI filter gain |
pu |
Parameter |
|
Small numerical regularization constant |
pu |
Parameter |
|
Angular frequency used by the SOGI filter |
rad/s |
Parameter |
|
Nominal per-phase active power setpoint |
pu |
Parameter |
|
Nominal per-phase reactive power setpoint |
pu |
The phase placeholder means each enabled star branch or active delta phase pair. The explicit A/B/C rows appear only when those conductors are selected; neutral ports appear only for a neutral-star configuration.
How to use itο
Use this template when you need an EMT load whose power changes with terminal voltage.
It is especially useful when ZIP composition matters more than machine-type load dynamics.
Verify the initialized total power and injection sign after choosing phases and connection.
Retain a positive
epsand inspect deep-fault behavior: regularization prevents singular current but does not define missing physical load-disconnection behavior.